HOME » Products » AC Moulded Case Circuit Breaker » Moulded Case Circuit Breaker » 3P 4P CDM3 MCCB Molded Case Circuit Breaker

3P 4P CDM3 MCCB Molded Case Circuit Breaker

The new CDM3 series of molded case circuit breaker products have a new industrial appearance design, which makes the products show a fashionable and atmospheric sense of quality; product specifications, CDM3 can provide nine types of case frame current specifications, covering from 63A to 1250A; the compact product volume, as well as the accessory independent installation function brought about by the removable design of the face cover, which greatly improves the product's convenience; and its excellent performance and innovative technology are leading the industry change; whether it is the traditional panel cabinet factory, the construction market, or the power market, OEM market, it can meet the needs of customers in many ways. Its excellent performance and innovative technology are leading the industry change; whether it is the traditional panel cabinet factory, construction market, or power market, OEM market, it can meet the needs of customers in various aspects.
Availability:

PDF Export

facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
sharethis sharing button

Product Overview

Pollution Level

● The CDM3 series operates in pollution class 3.

● The CDM3 series operates in a pollution class 3 environment (industrial environment) as defined by the IEC 60947-1 and 60664-1 standards.


Resistance to Heat and Humidity

● Dry cold, dry heat, humid heat


Technical Parameters

Frame Current CDM3-63 CDM3-100 CDM3-125 CDM3-160
Rated Voltage Ue(v) 400/415 400/415/690 400/415/690 400/415/690
Rated Insulation Voltage Ui(v) 800
800 800 800
Rated Impulse Withstand Voltage Uimp(kV) 8 8 8 8
Rated Current In(A) 10-63 10-100 16-100 10-125 40-125 100-160
Number of poles Pole(3P.4P-A/B) 3/4 3/4 3 3/4 3/4 3


C F C F C L S F

Rated Ultimate Short-Circuit Breaking

Capacity lcu(kA)

50/60HZ AC 400/415V 25 50 25 50
25 35 35 50
50/60HZ AC 690V / / / 8 / 8 8 8
Electrical Life AC 400 / 415V 8000 8000 8000 8000


Frame Current CDM3-250
CDM3-400 CDM3-630 CDM3-800 CDM3-1250
Rated Voltage Ue(v) 400/415/690 400/415/690 400/415/690 400/690 400/415
Rated Insulation Voltage Ui(v) 800 800 800 800 800
Rated Impulse Withstand Voltage Uimp(kV) 8 8 8 8 8
Rated Current In(A) 100-250 200-400 400/500/630 630-800 700-1250
Number of poles Pole(3P.4P-A/B) 3/4 3/4 3/4 3/4 3
Electrical life AC 400 / 415V 8000
7500 7500 2500 2500



Previous: 
Next: 
  • Subscribe to Our Newsletter​​​​​​​

  • get ready for the future
    sign up for our newsletter to get updates straight to your inbox
Leave a Message
Contact Us